Universal Manifold System II and Controller

The Lighthouse UM-II and CONTROLLER are the most affordable solution in the market to monitor large areas for particulate contamination.

The UM-II and CONTROLLER collect data from up to 32 locations via multiplexed monitoring. Lighthouse’s manifold design allows shorter purge times, increasing the number of samples per day. Users configure and control the system and can view sampling data on the Manifold Controller. The Controller can be placed up to 4,000 feet from the Manifold to allow control and viewing of data from a more convenient location. The UM-II and CONTROLLER perform user programmable data sampling and will alarm should a low-flow condition occur.

The UM-II and CONTROLLER interface with Lighthouse particle counters and existing building automation and facility management systems, providing the lowest cost per point on the market.

Designed and built by Lighthouse, a name you can trust.

Universal Manifold System II and Controller Datasheets
Letter Size – Lo Res                                A4 Size – Lo Res
Letter Size – Hi Res: 1,974 KB                A4 Size – Hi Res: 1,953 KB

  • Multiplexed Monitoring of Up to 32 Locations
  • Color LCD Display
  • Localized Control
  • User Programmable Sampling
  • Localized Data Viewing (Current and Historical)
  • Low Flow Alarm
  • Reduced Purge Times
  • RS-485 MODBUS
  • Stainless Steel Construction
  • Building Automation
  • Facility Management Systems Interface
  • 2 Year Warranty
  • Cost Effective Price per Point
  • Easy System Integration
  • International Support
  • Low Cost of Ownership
  • Cleanroom Monitoring
  • Facility Monitoring
  • SMIF and FIMS Enclosure Monitoring
  • Cleanroom Performance Verification
  • Large Area Monitoring
  • Trend Analysis
  • Cleanroom Laundries
  • Cleanroom Packaging
  • Semiconductor
  • Aerospace
  • Hard Disk Drive Manufacturing
  • Pharmaceutical Packaging and Manufacturing

Specifications

Manifold:
Sample Ports: 32
Flow Rate: 3 CFM (84.9 LPM) per port (nominal)
Cross-Port Contamination:  
Particle Sample Tubing: Particle transport tubing 1/2” OD, 3/8” ID (1.25 cm OD, 0.94 cm ID)
Sample Tubing Length: Up to 115 feet (35 m) per port
Fittings Provided: 32 Barbed Port Fittings, 1/2” (1.25 cm) OD tubing connection
Power: 24 VDC
Dimensions: 21.6” (l) x 12” (w) x 12.75” (h)
Weight: 16 lbs 6 oz
 
Manifold Controller:
Compatible Software: Lighthouse Monitoring System; LMS Express, Express RT and RT+ software; communicates with most other manufacturers’ Building Automation Systems and Factory Automation Systems
Communications Protocol: RS-485/MODBUS
Dimensions: 5.75” (l) x 8” (w) x 6.75” (h)
Weight: 4 lbs 6 oz
 
Optional Manifold Blower:
Safety Provision: Automatic pump shut-off
Power: 208, 415 VAC - Three Phase
Dimensions: 15” (w) x 20” (h) x 16.7” (l) [47 x 38 x 51 cm]
Weight: 75 lb (34 kg)

Conditions

Operating: 50°F to 104°F (10°C to 40°C) / 20% to 95% non-condensing
Storage: 14°F to 122°F (-10°C to 50°C) / Up to 98% non-condensing

Accessories

Included: Operating Manual on CD; Fuses
Optional: Printed Operating Manual; Manifold Vacuum Blower; Isokinetic Sample Probes;
Sample Tubing; Data Cable; Air Flow Balancing Unit; 2-inch Reinforced Vacuum Tubing